Minimal Time Of Valve Closure For Fluid Transient In Water Transmission

Jiaying Yu,ChangYong Wu,Yixing Yuan
2010-01-01
Abstract:The valve operation is an important method to control the flow in the project of water transmission. It should be closed quickly when an emergency event happens. However, too quick valve closure will produce water hammer that may cause pipe burst. The minimal time of valve closure is formulated as an inverse problem of fluid transient, which is solved by the method of characteristic (MOC) and the golden segmentation with the pressure constraints. The pressure must meet the constraints at every pipeline instead of the position before the valve. In addition, the time that the valve could be closed is considered. The method had been applied on a project in northeast of China. The accident of bursting the pipeline had not happened when the pipeline was repaired. The result demonstrates that the method can solve the optimal time of valve operation and two-step valve closure is better than linear.
What problem does this paper attempt to address?