Analysis on subsequent nuclear boiling and dry-out during the start-up of a two-phase CO2 mechanically pumped thermal control system

Xinhui Sun,ZhenCheng Huang,Yue Chen,Wenjia Xiao,Zhenhui He,Johannes Van Es.,Aswin Pauw
2009-01-01
Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics
Abstract:A mechanically pumped CO2 two-phase thermal control loop (MPTCL), to effectively collect waste heat through dual evaporators and release heat through dual condensers with longer transport distance, is investigated on its start-up characteristic. These experiments indicated that (1) when using long capillary tubes as an evaporator to collect distributed heat resource with low heat flux at low operational temperature, the MPTCL shows that superheating followed by subsequent nuclear boiling, and temporal dry-out found somewhere in the downstream after nuclear boiling are accomplished in the upstream, and (2) comparing three different start up characteristic, balance heat load is relative better way for the MPTCL' start-up.
What problem does this paper attempt to address?