Experiment on Two-phase Cooling System with Dual-Evaporator Driven by Mechanical Pump

Liu Jie,Li Tingxun,Guo Kaihua,He Zhenhui
DOI: https://doi.org/10.3969/j.issn.0253-4339.2008.06.002
2008-01-01
Abstract:Experiments on start process and periodic boundary temperature change of a two-phase cooling loop driven by a mechanical pump were conducted to investigate the characteristics of the system. CO2 was adopted to be the working fluid in the system with a dual-evaporator. The results indicate that both sides of the evaporation section exhibited steady performance during start process. The fluid temperature in the each branch pipe changed in the same tendency and only superheat time was slightly different because of different pipe arrangement and gravity. The experiment of periodic boundary temperature change shows that the system could be effective to heat emission even if the boundary temperature fluctuation of the condenser was greater than 30℃, and the temperature difference of the evaporation section with the length of 12m was smaller than 0.5℃.