Experimental Study on a Dual- parallel-evaporator Heat Pump System for Thermal Management of Electric Vehicles

Guiying Zhang,Fei Qin,Huiming Zou,Changqing Tian
DOI: https://doi.org/10.1016/j.egypro.2017.03.687
2017-01-01
Energy Procedia
Abstract:A dual-parallel-evaporator heat pump system, which has two parallel evaporators for cabinet air-conditioning and battery temperature control respectively, is designed to realize thermal management for electric vehicles. System performance and refrigerant mass flow distribution character of two branches at different opening degrees of electric expansive valve are tested. Changes of refrigerant superheat degree and pressure at the outlet of battery side evaporator caused by the decreasing of the battery temperature have great effect on mass flow rate of cabinet branch. The maximum mass flow rate reduced ratios of cabinet branch is 20.5% when the opening degree of electric expansive valve (EEV) of battery branch is 0.3. Stable performance of this system on rated condition is tested by adjusting the opening degree of two EEVs to get the optimal status. The experimental results indicate that integration operation can supply additional 1.04kW cooling capacity for battery unit with very little compressor power increase. However, cooling capacity of cabinet side only decreases by 0.95%. The additional parallel evaporator is desirable to solve the battery cooling problem. (C) 2017 The Authors. Published by Elsevier Ltd.