Simulation and Analysis of Building Dynamic Performance in Heat Metering Systems

XU Baoping,FU Lin,DI Hongfa
DOI: https://doi.org/10.3321/j.issn:1000-0054.2008.03.001
2008-01-01
Abstract:The factors influencing the flow rate in hot water heating system in residential building with heat metering systems using thermostatically controlled radiator valves were analyzed by modeling the building heating system.The main factors affecting the flow rates are the solar radiation,the outdoor temperature,and consumer behavior for district heating systems with a constant water supply temperature.The calculational results show that during a typical day in Beijing the relative flow rate fluctuations are about 30% in buildings where consumers do not adjust the thermostats and from 60% to 90% when 50% of the consumers in the building adjust the thermostats according to a schedule.
What problem does this paper attempt to address?