Test and analysis on variable flow rate in a heat metering quarter

Xu Baoping,Fu Lin,Di Hongfa
DOI: https://doi.org/10.3969/j.issn.1002-8501.2008.01.028
2008-01-01
Abstract:Performs the test and analysis in a residential quarter with household heat metering system on the basis of different space and time scales.The results show that the flow rate of users varies considerably with a maximal changing range of relative flow rate from 0 to 100 percent;that the changing range decreases along with the enlargement of space scale from end-users to buildings and stations;that the fluctuation of relative flow rate of stations is less than 2.5 percent in an hour,5 percent in a day and 10 percent in a controlled period and presents a step changing trend during a whole heating season because of the pressure differential control;and that the pump consumption is related with the set value of differential pressure.