Simulation and Analysis on Intermission Heating of Office Buildings in Beijing

Bao-ping XU,Ling HAO,Lin FU,Hong-fa DI
DOI: https://doi.org/10.3969/j.issn.1002-8528.2011.08.012
2011-01-01
Building Science
Abstract:In this paper,for the heating system in office buildings with comfort indoor temperature only during working period,a control strategy which could adapt the heating load variations by adjusting warm-up time and cool-down time during each operation period was proposed to reduce the system runtime.A typical office building in Beijing was selected as the research object and was simulated under different conditions of building envelope insulation,terminal form and climate situation.Simulation results of design heating load,energy-saving effect,room temperature variation trend and transition time were analyzed.The main conclusions were as follows:in order to ensure each room had same warm-up time,the biggest heating capacity for each room should be 1.1~1.3 times of the traditional design heating load,energy-saving rate could reach at 25%~40% in a typical week when intermission heating mode was adopted,the mean room temperature was 18 ℃ and the lowest value was 17 ℃ under the intermission heating mode,the lowest room temperature was 4 ℃ when the heating system was cut-off,the warm-up time under different conditions had large distinction,it varied from several minutes to several hours.