Statistical Analysis of PD Pulse Occurring in XLPE Insulation During Its Electrical Aging

CHEN Xiao-lin,HUANG Hong-xin,CHENG Yong-hong
DOI: https://doi.org/10.3969/j.issn.1003-6520.2007.08.003
2007-01-01
Abstract:In order to understand the physical mechanisms of partial discharge(PD) in insulation,the accelerated electrical aging tests of XLPE specimens were performed and an ultra-wideband(UWB) PD measurement system was adopted to study the characteristics and mechanisms of PD in XLPE during electrical aging.The bandwidth of the UWB PD measurement system spans the frequency range from 10MHz to 3GHz.The UWB PD pulses were analyzed by a statistical method,by which the shape parameters of the PD pulses,the parameters of rise times,fall times,and amplitudes were analyzed.These shape parameters were helpful to evaluating the PD mechanisms and the aging status.The results showed that the single waveform parameters changed greatly in the different aging stages,such as fall time and pulse amplitude.The rise time varied slightly during aging,while the fall time changed greatly,increasing from about 15ns before aging to about 90 ns after aging for 50 hours.The PD pulse amplitude was about 1000 mV when the specimens were in the virgin stage.It fell down after aging for several hours,and it decreased at the value about 200 mV after aging for 15 hours.And then,it increased if it was further aging and was about 500 mV after aging for 30 hours,about 600 mV for 50 hours.The rising edge was steep and the fall time was short before aging,so it was supposed that the streamer discharges took place.And the fall time was long when aging severely,therefore the PD mechanism was supposed to be Townsend discharges.