Experimental Study on Partial Discharge in XLPE Insulation During Electrical Aging
Xiaolin CHEN,Yonghong CHENG,Xiaojun XIE,Hao CUI
DOI: https://doi.org/10.3969/j.issn.1003-6520.2006.04.008
2006-01-01
Abstract:The XLPE insulation samples are processed by an accelerated electrical ageing setup, and the characteristics of partial discharges (PD) during ageing are studied by the TE571 PD detector and the ultra-wide band PD measurement system. The TE571 PD detector detects the phase resolved PD signals, such as the phase resolved distribution of the maximum discharge magnitude, the mean discharge magnitude, and the number of discharges, while the ultra-wide band PD measurement system acquires the time-domain pulses of PD and obtains the PD waveform parameters, such as the rise times, fall times, and amplitudes of PD pulses. Thus, the statistical parameters and single waveform parameters are obtained respectively, and the former can also be used to evaluate the aging status of the XLPE samples. The experimental results show that the rising edge of PD pulses become steep, which decreases from 50 ns before aged to 8 ns after aged for 50 hours, the amplitude of PD pulses increases from 2 mV to 17 mV, and the characteristic peaks location in the spectrum move toward to high frequency band, which shift from below 15 MHz before aged to 50 MHz and 125-200 MHz. This research is a foundation for evaluating the insulating status of XLPE power cables in service.