Study of Discriminating Approach for Switching into Fault Line in Ultra-high-speed Protection

DUAN Jian-dong,LUO Si-bei,ZHANG Bao-hui,XUE Jing
DOI: https://doi.org/10.3321/j.issn:0258-8013.2007.10.013
2007-01-01
Abstract:It is vital but difficult for ultra-high-speed (UHS) protection to reliably identify whether there is a line fault when a circuit breaker closes into a transmission line. This paper firstly indicates that circuit breaker closure can be simplified to unloaded closure for UHS protection. Then the paper analyzes the different features of the circuit breaker switching into a normal or faulted line. On one hand, the difference lies in the arriving interval and polarity relation between initial forward and backward traveling waves at protection location. On the other hand, the difference also lies in the voltage/current self-oscillating features. Besides, the different polarity relations of initial forward and backward traveling waves are discussed respectively in phase domain and modal domain. Based on these different features, the paper proposes the discriminating approach of circuit breaker switching into faulted lines, and presents the corresponding discriminating algorithm based on wavelet transform. ATP simulation tests show that this approach is feasible and reliable.
What problem does this paper attempt to address?