A Novel Traveling-Wave-Based Main Protection Scheme For +/- 800 Kv Uhvdc Bipolar Transmission Lines

Fei Kong,Zhiguo Hao,Baohui Zhang
DOI: https://doi.org/10.1109/TPWRD.2016.2571438
IF: 4.825
2016-01-01
IEEE Transactions on Power Delivery
Abstract:The UHVDC transmission system has been increasingly used because of the advantages in long distance and large capacity transmission. However, the existing traveling-wave-based protection for UHVDC transmission lines is not sensitive enough to properly detect the internal fault with high fault resistance. A novel traveling-wave-based protection scheme for bipolar UHVDC lines is proposed in this paper. The discriminative characteristic between the internal and external fault, embodied in the backward traveling wave, is extracted to formulate the main protection criterion. The faulty line is identified by the polarity of the voltage fault component. In addition, only the single-pole voltage and current of rectifier side are required for the proposed protection scheme. The simulation and field data tests show that the proposed protection scheme can make a correct identification of the fault section and selection of the faulty line in the +/- 800 kV UHVDC system and +/- 500 kV HVDCsystem. Besides, the proposed protection can correctly detect the grounding fault with fault resistance up to 500 Omega.