Development of relay protection for smart grid(1): new principles of fault distinction

Baohui Zhang,Zhiguo Hao,Zhiqian Bo
2010-01-01
Abstract:As the fault transient components have same power directions at both line ends and great transient energy during internal line faults, they can thus be extracted by the wavelet transform and applied in the ultra-high-speed protections for EHV transmission line and bus. When the DC filter and smoothing reactor are installed at the ends of DC line to form an impedance boundary of high frequency components, which makes the high frequency components of internal fault signals much greater than those of external ones, the energy of them can thus be used to realize the ultra-high-speed protection for UHVDC transmission line at single end. As the transient zero-sequence component is several ten times larger than the power frequency component and not reduced by the compensation during the single-phase-to-ground fault in a neutral indirectly grounding power system, the high frequency component of zero-sequence current is thus extracted to realize the grounding line selection by comparison of direction and amplitude. Tests show that the fault kind can be determined with ultra-high -speed (within 5 ms) and the new principles of fault distinction can satisfy the demand of EHV system for ultra-high-speed fault removal in smart grid.