Failure Protection Strategy of UHVDC Circuit Breaker Under Phase Shift Control

SONG Hailong,YE Dongmeng,SHI Lei,LIANG Tianyu,CHAI Bin,YANG Songhao,HAO Zhiguo
DOI: https://doi.org/10.13296/j.1001⁃1609.hva.2023.05.003
2023-01-01
Abstract:For ultra-high voltage direct current(UHVDC)projects,the use of converter phase-shift control after a fault inside the converter protection zone is helpful for fault current limitation and isolation. Horever,the adaptability of circuit breaker failure protection based on current characteristics is significantly reduced.Therefore,on the basis of analyzing the failure characteristics of circuit breakers in the time and frequency domains,the research idea of failure diagnosis through the energy distribution of voltage signals in different frequency bands is proposed in this paper. Moreover,the complementary ensemble empirical mode decomposition(CEEMD)and Hilbert-Huang transform are combined and,on the basis of considering the tailing phenomenon of the instrument transformer,a kind of new principle of circuit breaker failure protection based on the voltage integral value of different frequency bands is proposed. Finally,the follow-up operation strategy after the failure protection operation is formulated.The simulation verification shows that the failure protection principle has met rapidity and reliability requirement,and the follow-up operation strategy has achieved the rapid isolation of the fault and significantly improved the performance of the converter area protection.