Experimental Study of Wet Flue Gas Desulphurization of Impinge Liquid Column Tower

CHENG Feng,LUO Zhong-yang,GAO Xiang,WANG Jun,GUO Rui-tang,CEN Ke-fa
DOI: https://doi.org/10.3785/j.issn.1008-973x.2005.11.028
2005-01-01
Abstract:A new type of impinging liquid column tower for wet flue gas desulphurization(WFGD) was built in laboratory.The effects of different geometry and operation parameters on the desulphurization efficiency in the scrubbers were studied on an experimental platform.The main influencing factors include: slurry flux density,flue gas velocity,pH in the circulating tank,inlet mass concentration of SO_2,temperature of the inlet flue gas,and the configurable factors such as height of block and cross-section of scrubber.The results indicate that the desulphurization efficiency increases with increasing slurry flux density,flue gas velocity,pH in the circulating tank and inlet temperature of the flue gas,but that the efficiency decreases with increasing inlet mass concentration of SO_2. Decrease of the scrubber cross-section or the distance between the impinging plate and the nozzle results in better atomization,which greatly increases the desulphurization efficiency.With optimized geometry and operation parameters,the desulphurization efficiency can be improved to 95%.
What problem does this paper attempt to address?