Study on the Heat Transfer Enhancement of Two-Phase Flow Elevation Tube in LiBr Chiller with Hot Water Source

张联英,吴裕远,郭金刚,陈东升
DOI: https://doi.org/10.3321/j.issn:0253-987X.2004.01.002
2004-01-01
Abstract:Experiments on boiling heat transfer and thermosiphon elevation of LiBr solution inside three lunate channels with different diameters were performed. The experimental results showed that the dimension of the lunate channel had a direct influence on the heat transfer and solution elevation. The elevating tube, whose diameter ratio of two pipes is 19:32, has the best elevation effect among them, and its net elevating height of solution is 2.5 times as high as that of the solution submergence. The elevating height is the highest in China, and at the same time the temperature of the heat source driving the generator is 10°C, which is lower than others. The distilled water yield and vapor fraction at outlet of the elevating tube increase with the heating water temperature and heat flux. The vapor mass fraction at the outlet of the elevating tube increases with the decrease of the driving liquid head.
What problem does this paper attempt to address?