A NOVEL PRINCIPLE OF SINGLE-ENDED LINE FAULT LOCATION TECHNIQUE FOR EHV TRANSMISSION SYSTEMS

哈恒旭,张保会,吕志来
DOI: https://doi.org/10.3321/j.issn:0258-8013.2003.02.009
2003-01-01
Abstract:A new fault location algorithm using derived information of one terminal is proposed in the paper, based on distributed parameter line model. As to a healthy line, using traveling wave theorem, one can get the voltage along the line using single-ended data. However, it is not the ease to a faulted line, the computed voltage at the point behind the fault point using the single-ended data is not true, we call the computed voltage as Fictitious Voltage Profile. By our analyzing the relations between the Real Voltage profile and Fictitious Profile, it is concluded that, the minimum norm value of derivative of real voltage and fictitious to distance is at the same point, that is, at fault point. Therefore, the fault location algorithm is proposed as following: (i) compute the fictitious voltage along the line using the single-ended data; (ii) compute the norm value of derivative of the fictitious voltage at each point and search the minimum point, which is the fault point. The EMTP simulation tests show that the algorithm has the quality of more accurate; however, some problems should be solved later.
What problem does this paper attempt to address?