A Novel Phase Comparison Algorithm for Single Terminal Fault Location Based on Distributed Parameter Model

LIN Xiang-ning,HUANG Xiao-bo,WENG Han-li,LU Wen-jun
DOI: https://doi.org/10.3321/j.issn:1000-3673.2007.09.015
2007-01-01
Abstract:Single-phase earth faults are in the majority of all faults occurred in EHV and UHV transmission lines,the research on accurate fault location of single-phase earth fault is significant.The lumped parameter model based single terminal fault location algorithm neglects the influence of distributed capacitance,so it brings bigger location error while fault occurs at a distant position.For this reason,the authors propose a distributed parameter model based single terminal fault location algorithm using phase comparison of voltage and current,that is,by means of phase and modular transformation and inverse transformation the distribution of voltage and current of faulty phase at all points along the line is estimated,then the fault is located according to the feature that at the faulty position the phase angle difference between the residual voltage and fault-component of current should be the least.The proposed algorithm uses power-frequency voltage and current only,so lower sampling rate is suitable and this algorithm can be easily implemented by existing protection devices.The effectiveness of the proposed algorithm is verified by a lot of ATP simulation results.
What problem does this paper attempt to address?