A SOLUTION TO INFLUENCE ON FAULT LOCATION BY SATURATION OF CURRENT TRANSFORMER

陈铮,董新洲,罗承沐
DOI: https://doi.org/10.3321/j.issn:1000-1026.2002.01.009
2002-01-01
Abstract:Current transformer (TA) saturation may cause great errors of fault location based on power frequency quantities. A method using an artificial neural network (ANN) is presented to correct the distortion of current transformer secondary current caused by the TA saturation. Moreover, a forward BP network is developed through MATLAB program. So the ANN can be trained to achieve an inverse transfer function of iron-core toroidal current transformers widely used in protection system. Consequently the compensated currents are suitable for fault location. The simulation results of EMTP show that the compensation of saturated current by ANN can significantly improve the accuracy of fault location.
What problem does this paper attempt to address?