Relationship between harmonic coefficients definition and power-step number of controllable reactor of transformer type

Mingxing Tian,Xiao An,Dongsheng Yuan,Shengjie Gu
DOI: https://doi.org/10.13335/j.1000-3673.pst.2014.01.034
2014-01-01
Abstract:Power-step number of controllable reactor of transformer type (CRT) is determined by reactive power increment coefficient, and the reactive power increment coefficient is determined by harmonic coefficients. Three kinds of harmonic coefficients are defined, and the relationship between harmonic coefficients and power-step number is quantitatively analysed according to the three definitions, then the calculation formulas are given; the results of numerical examples are compared and analysed. The results show that, under the premise of meeting the harmonic current limiting requirements, the power-step number calculated according to the three definitions of CRT is decreased sequentially, and the RMS of maximum harmonic current is increased sequentially. At the same time, in view of the RMS of harmonic current, it is not reasonable that the harmonic coefficient calculated by the first definition will lead to too many power-step number, and it is the most reasonable that the harmonic coefficient calculated by the third definition will obtain the least steps. The work of this paper lays a theoretical foundation for simplifying the structure of CRT, meanwhile, provides a reference for design and harmonic analysis of similar electrical equipment.
What problem does this paper attempt to address?