Capacity configuration of V/V transformer-based railway power conditioner and optimal energy compensation strategy

Xin Zhang,Quanyuan Jiang
DOI: https://doi.org/10.3969/j.issn.1006-6047.2014.01.018
2014-01-01
Abstract:Aiming at the harmonic current and negative sequence current of high-speed railway traction power supply system, an optimal energy compensation strategy based on RPC (Railway static Power Conditioner) is proposed and the detection method of harmonic and negative sequence currents in optimal compensation condition is discussed. The optimal steady-state power of RPC is analyzed according to its compensating energy and three performance indexes are proposed: active power compensating degree (��), reactive power compensating angle (��) and harmonic current compensating degree (��). PSO (Particle Swarm Optimization) algorithm is used to calculate these three indexes for the minimum compensating energy. The optimal energy compensation is realized by controlling three indexes. The capacity of RPC is configured by the optimal energy compensation strategy. An application to real time compensation is proposed. Simulative results show that the RPC capacity is reduced due to the optimal energy compensation strategy.