Study on Elimination of 5 th and 7 th Harmonics by TCT Type Adjustable Reactor

Heng WANG,Yan ZHAO,Xiaojun LIU,Xiaojun ZHANG
DOI: https://doi.org/10.3969/j.issn.1674-1757.2014.02.015
2014-01-01
Abstract:In this paper,for solving the 5th and 7th harmonics generated by the TCT ( thyristor con-troled transformer ) type adjustable reactor of Dyn connection and achieving good application of the e-quipment,the double secondary winding control mode is used to offset the 5th and 7th harmonics gen-erated by the equipment by way of phase shift .And test circuit is set up for validation .It is shown by the result that the elimination ratio of the 5th and 7th harmonics in the double secondary winding is a-bove 90%,which assures economic operation of the equipment .