Analysis on winding current of controllable reactor of transformer type
Mingxing Tian,Dongsheng Yuan,Xiao An,Jianning Yin
DOI: https://doi.org/10.13336/j.1003-6520.hve.2014.01.040
2014-01-01
Abstract:In order to improve the efficiency of controllable reactor of transformer type, we analyzed the winding current. Based on the grading principle of step-single-branch operation mode, taking the self and mutual leakage reactance of all windings into account, we derive the functions of winding current, rated current utilization and equivalent leakage reactance, and propose a requirement in equivalent leakage to make the reactor efficient. Meanwhile, through an example, we demonstrate that the equivalent leakage reactance influences the winding current distribution and lowers the rated current utilization, so the design of reactors should follow the principle of minimizing leakage reactance. Some other conclusions are also drawn: the current utilization would fulfill the design requirement when the equivalent leakage reactance is less than the maximum value that is determined by the power increment coefficient, the required utilization of rated current, the capacity ratio of the first level control winding, the winding number, and the short-circuit reactance. In this case, the controllable reactor of transformer type could work efficiently.