Lightning Scope Division and Lightning Trip-out Rate Calculation Method for Overhead Catenary System

CAO Xiaobin,XIONG Wanliang,WU Guangning,LI Ruifang,ZHOU Lijun
DOI: https://doi.org/10.3969/j.issn.1003-6520.2013.06.033
2013-01-01
Abstract:In order to evaluate the reliability of traction power supply system struck by lightning,we divided lightning strokes into three types according to the way of lightning over-voltage production,and proposed that the lightning stroke type was decided by the position of lightning leader.Combined with the basic principle of the electrical geometry model(EGM),EGMs of single-line section and double-line section of railway were established.Then the exposure arc range of return line and catenary wire were given,and coordinates equations of each exposure arc's intersection were derived.By using these equations,work ranges of different lightning types were obtained.Furthermore,taking the recommended calculation formula of lightning current amplitude distribution and construction of arc rate in DL/T 620—1997 into consideration,we proposed formulas of trip rate for the three lightning stroke types and an assessment method of total trip rate.After calculating the trip out rate of an electrified railway by the method,we found a phenomenon that the lightning trip rate of double-line section was lower than that of single-line section in a direct power supply system.Further analysis indicated that the shielding effect of return line on catenary was the main reason for this phenomenon.