Analysis of Lightning on the Feeder Side of GIS Traction Substation

ZHANG Xian-yi,WU Guang-ning,CAO Xiao-bin,LUO Xun,GONG Hong-kui,GAO Feng,X ZHANG,X CAO,X LUO,H GONG,F GAO
DOI: https://doi.org/10.16188/j.isa.1003-8337.2013.05.017
2013-01-01
Abstract:Breakdown will occur on the insulator when lightning strikes on the feeder side of traction substation.The impinging surge caused by lightning back flashover will propagate along the line to the equipment in the traction substation resulting to overvoltage which will threat the operation and transportation safety.By use of ATP-EMTP to take the lightning simulation calculation,the protection effect of the arrester is verified.The wave front steepness increases with the length increased of the electric cable.The influence of feeder line length on the impinging surge overvoltage is analyzed,and the key factor is the number of broken down insulators.The higher of the broken down insulator number,the lower of the overvoltage magnitude on the equipment.
What problem does this paper attempt to address?