Study on Calculation Method of Lightning Trip-out Rate of AC Overhead Transmission Lines

YIM Qin,GUO Jie,CHEN Jie,WANG Sen,WANG Li-ying
DOI: https://doi.org/10.3969/j.issn.1003-8337.2012.03.015
2012-01-01
Abstract:There are many ways to calculate lightning trip-out rate of A.C.overhead transmission lines,because the difference of the model and the initial parameter,the results are quite different.For this problem,taking 110 kV,330 kV triangular arrangement overhead transmission lines and 330 kV,750 kV overhead transmission with double-circle line in Shannxi 110 kV,330 kV,750 kV high voltage transmission projects as examples,lightning trip-out rate of overhead transmission lines are calculated by method of electrical geometric model(EGM),method of EMTP simulation,method of DL/T620—1997[1].Comparative analysis of the calculation results are carried out combining with years of observation data of lightning trip-out rate,reference is provided for choosing appropriate calculation method.