Single-phase-to-ground Fault Location Based on Transient Fault Signal and Its Attenuation Character for Distribution Network

ZHANG Wenhai,XIAO Xianyon,WANG Ying
DOI: https://doi.org/10.3969/j.issn.1006-6047.2013.03.008
2013-01-01
Abstract:A method of single-phase-to-ground fault location is proposed based on the transient fault signal and its attenuation character.The transient signal of line capacitive charging caused by the voltage rising of healthy phases during the single-phase-to-ground fault of noneffectively earthed system at neutral point and its attenuation character are used to adaptively identify the effective segment of the transient signal and calculate the fault distance.It makes full use of the transient signal.The real wavelet transform,complex wavelet transform and S transform are applied to extract the transient character of charging signal and calculate the fault distance respectively.Comparison and simulation show that the S transform is the best. With the measurements of single end only and little effect by the fault distance,fault voltage initial angle and noise,the proposed method locates the grounding fault effectively when the fault resistance is smaller due to the large magnitude of transient signal.
What problem does this paper attempt to address?