Analysis on the wall sub-cooling of heat trans fer of steam condensation with non-condensable air

Jiqiang SU,Zhongning SUN,Li GAO,Guangming FAN
DOI: https://doi.org/10.3969/j.issn.1006-7043.201212052
2013-01-01
Abstract:For the purpose of conducting safety analysis on nuclear reactor accidents , experiments were done with heat transfer of steam condensation containing air on the outside surface of a vertical tube .The emphasis of the anal-ysis is concentrated on the wall sub-cooling.The research also includes the relationship of heat transfer of steam condensation with such parameters as air mass fraction , pressure, and wall sub-cooling.The results show that, un-der the experimental conditions , the relationship between wall sub-cooling and the coefficient of heat transfer of condensation (HTC) is exponential.The value of the exponent is less than -0.39, which is less than that of Dehbi's result and the influence on heat transfer found in this experiment is stronger .The influence of wall sub-cool-ing on HTC increases with the decrease in pressure , increasing of air mass fraction as well as the increase in wall sub-cooling , and the relationship curve is obtained .Based on the analysis of the wall sub-cooling , the experimental correlation between the influence of the air mass fraction , pressure , and wall sub-cooling on HTC is obtained .
What problem does this paper attempt to address?