Integrated control strategy of three-phase four-wire shunt active power filter using multiple converters

杨晓利,葛宝明,姜新建
2012-01-01
Abstract:In order to improve the control effect of high-power shunt active power filter, the paper uses detection algorithm for selective harmonic current in three-phase four-wire system. The algorithm can detect positive, negative and zero phase-sequence component of the random harmonic current, and can improve the accuracy and real-time of the harmonic current detection. At the same time, the paper presents a dual closed-loop control strategy to suppress the circulating current brought about by the multiple structure of the main circuit. The grid side filters use LCL-filter. Compared to traditional L-filter, the LCL-filter has better filter performance not only in effectively filtering the high frequency switching harmonics of the main circuit, but also in reducing the value of inductance, improving system dynamic performance and reducing the cost. Finally, the paper sets up a simulation model and an experimental prototype of the system, and the results show that the control strategy is correct and feasible, and harmonic treatment of the system is effective.
What problem does this paper attempt to address?