Mechanical & Thermal Stress Analysis under Actual Condition and Test Design of 550kv High Coupled Split Reactor
Li Zhao,Yanzhe Zhang,Tong Jiang,Qiang Tang,Haojun Liu,Wenbo Yu,Zhao Yuan,Wenxiong Mo,Haibo Su,Le Gu,Shixin Xiu,Shenli Jia
DOI: https://doi.org/10.1109/ei250167.2020.9347258
2020-01-01
Abstract:The phenomenon of 500 kV line short-circuit urrent exceeding the protection scope of circuit breaker is seriously threatening the safety of power grid, and installing a suitable fault current limiter is an effective method to deal with such problem. 550 kV high coupled split reactor studied in this paper is an important component of 500kV fault current limiter that is desighed with new technology. It has the functions of withstanding and limiting short-circuit current, and has the advantages of high flexibility, easy maintenance and low loss. However, at present, there is a lack of relevant literature and standards to guide this type of equipment for the evaluation of mechanical and thermal stress under actual conditions. This paper studied the actual working conditions of 550kV high coupled split reactor, analyzed its current characteristics, and on this basis, performed steady-state temperature field simulation analysis at rated continuous current and stress calculation during short circuit, and proposed a scheme for equivalent test using a small prototype in the actual conditions of the laboratory. This paper is beneficial to the design and testing of such equipment in the future.