E-field Distribution and Optimization on Shielding Electrodes for Reactor in ±1100 kV Indoor DC yard

Zehua Wu,Huidong Tian,Jialong Wang,Shoufeng Jin,Peng Liu,Zongren Peng
DOI: https://doi.org/10.1109/ceidp47102.2019.9009850
2019-01-01
Abstract:Due to the complex structure and the area constraints of indoor DC yard, electric field distortion on the surface of shielding electrodes occurs more frequently. As a key device, reactors bear 1100kV operation voltage and play a role of filtering harmonics in indoor DC yard. Thus the electric field distribution characteristics of reactors should be paid attention to. In this paper, based on the design drawings, a 3-dimension model of the whole ± 1100kV indoor DC yard was built to simulate the actual situation and the E-field was calculated by ANSYS. On the basis of this, trapezoidal arrangement which deploys smaller ring distance and diameter, larger tube diameter was put forward. The maximum field value with trapezoidal arrangement on the surface of shielding electrode decreased from 1329.8 V/mm to 1155.3 V/mm, which made the design meet the requirement of critical strength. In addition, electric field distributions of three types of shielding rings for outlet devices are compared and analyzed. The influence of ring spacing on electric field was also investigated. Large ring spacing can lead to field distortion dramatically on the beneath ring. Considering electric field distribution and installation, scheme 2 with smaller ring spacing is firstly recommended for the UHVDC reactors. The calculation results could provide a valuable reference for the design of UHV DC yard.