Simulation Research on Influence of SVC Switching Overvoltage on Phase Controlled Reactor

Jun Min Li,Jiang Tao Li,Xin Yu,Shu Han Wang,Si Cong Wu
DOI: https://doi.org/10.4028/www.scientific.net/amm.602-605.2966
2014-01-01
Applied Mechanics and Materials
Abstract:In recent years, 66kV vertical TCR-type SVC was put into operation in several transformer substations at home. Compared to the compensation mode of the conventional 35kV SVC which is connected to 66kV busbar through by way of step-down transformer, the vertical compensation mode has the advantages of low loss and small maintenance amount. However, it is found that damage of phase controlled reactor in TCR happens in several scenes, and the technicians and research institutions studied this problem from such aspects as phase controlled reactor manufacturing process, SVC control strategy and natural environment of the transformer substations and obtained their own conclusions. This paper uses PSCAD software to conduct a simulation research on the 66kV vertical SVC system installed on a 220kV transformer substation at home and concluded that the SVC switching overvoltage might be the direct cause leading to damage of phase controlled reactor.