New evaluating index for seasonal performance and performance evaluation for multiple chillers combined operation

Wu Chengbin,Shi Wenxing,Li Xianting
DOI: https://doi.org/10.3969/j.issn.1002-8501.2012.08.002
2012-01-01
Abstract:Integrated part load value(IPLV) is an important index to evaluate the seasonal performance of chillers.However,there are still some disputes over the rationality of IPLV.According to the physical nature of the index,puts forward a new index,seasonal part load value(SPLV) for evaluating seasonal performance of a single chiller.Based on the evaluating idea of SPLV,presents a method for calculating the seasonal part load value SPLV(N) of multiple chillers combined operation and its work condition.Evaluates different kinds of chillers with SPLV(N).The result shows that SPLV can better reflect the true season operation performance of chillers;the value of SPLV(N) has a close relationship with the performance curve of the chillers and different kinds of chillers have their suitable application modes.
What problem does this paper attempt to address?