Research on IPLV (H) for Low Temperature Air Source Heat Pump (Water Chilling) Packages

Wang Jia,Xie Qiao,Shi Wenxing,Zhang Leping
DOI: https://doi.org/10.3969/j.issn.0253-4339.2008.06.003
2008-01-01
Abstract:The evaluation method of heating integrated part load value (IPLV (H)) in the standard on low temperature air source heat pump water chilling packages was investigated to determine weight coefficients in the IPLV (H) equation, the test condition of the part load ratio, and the test method of heating COP (COPh) in each load ratio according to the meteorological data and building load in the cold area. It concludes that the IPLV(H) equation for the cold area in North China can be IPLV(H)=0.083×A+0.403×B+0.386×C+0.129×D. In addition, the test conditions and methods in 100%,75%,50% and 25% load ratio were presented.
What problem does this paper attempt to address?