Comparison between SPLV and IPLV for evaluating water chiller performance

Wu Chengbin,Shi Wenxing,Li Xianting,Wang Baolong
2012-01-01
Abstract:Puts forward a new index-seasonal part-load value(SPLV) based on the physical meaning that the performance index should be equal to the ratio of total seasonal cooling capacity to total power consumption.Analyses the differences and relation in respects of the formula form,index value and application of SPLV and IPLV to the typical characteristic curves.Concludes that SPLV and IPLV adopt the same constituent elements with different formula form and dimension.For the same chiller unit,IPLV is greater than or equal to SPLV,and the larger the difference among COPc of part-load working condition points is,the greater the deviation between IPLV and SPLV is.