Experimental Investigation of Heat Transfer and Energy-saving Operation of an Air-cooled Closed Circuit Cooling Tower

QIAN Tai-lei,WU Jia-fei,ZHU Dong-sheng,ZHENG Wei-ye,LI Xia,ZHOU Hong-jian
DOI: https://doi.org/10.3969/j.issn.1005-0329.2013.06.015
2013-01-01
Abstract:An experimental test platform is built up to for the twisted tube closed circuit cooling tower.The principal of this study is to investigate the influence of fan frequency,volume flow rate,the temperature of environment and tube-inside fluid on the total heat transfer performance and air-cooled heat transfer quantity by testing the heat transfer performance,resistance to flow and energy consumption at different fan-frequency,inlet temperature of process water and air dry ball temperature in the air-cooled mode,then get the method to optimize the heat transfer in air-cooled Closed Circuit Cooling Tower,to obtaine the most reasonable working mode interface different temperature.This experiment also fit out the experimental correlation of fan-frequency,fan-power with the face velocity as well as the experimental heat transfer coefficient correlations of the air outside the tube,and this correlation will be referred in optimal design for twisted-tube closed circuit cooling towers.
What problem does this paper attempt to address?