HEAT LEAK EFFECTS ON THE HEAT TRANSFER PERFORMANCE OF A FLAT LOOP HEAT PIPE

MO Dong-Chuan,DING Nan,Shushen Lü
2010-01-01
Journal of Engineering Thermophysics
Abstract:Loop heat pipes now become the front technology for the high heat flux thermal cooling as its excellent heat transfer performance.In this paper,we manufactured a loop heat pipe with flat evaporator,using copper as shell and ultra pure water as the working fluid.The heat leak effects on the heat transfer performance of a loop heat pipe had been studied experimentally.Reducing the equivalent thermal conductivity of the wick material can reduce the heat leak,by which the loop heat pipe gives better performance.Results show that,the loop heat pipe with flat evaporator can transfer 150 W to a distance of 80 cm with thermal resistance of 0.08℃/W.The lowest start power is 2 W in the test,and the loop heat pipe can start up easily.
What problem does this paper attempt to address?