Fire Experimental Study of Upright ESFR Sprinkler for Protection of High-rack Storage

Yi LI,Xin LIU,Qiang ZHANG,Jian-qiang WANG,Li-wei TIAN,Zhen-yu WANG
DOI: https://doi.org/10.3969/j.issn.1003-3033.2011.12.006
2011-01-01
Abstract:Full scale fire tests of 5-tire and 6-tire rack storage under 10.5 m ceiling were carried out to study the performance of K202 upright ESFR sprinkler on the protection of high-rack storage and the effect of sprinkler pipe on the fire suppression.Parameters as sprinkler actuation time,number of sprinklers to open,ceiling temperature,steel angle temperature above the ignition and equivalent number of commodities consumed were measured.The results show that: not more than 3 sprinklers will open quickly in the early period of the fire,and fire can be suppressed obviously after sprinkler actuation;during the test there is no fire jump to the target array.It is found out that K202 upright sprinkler is effective for the protection of high-rack storage with commodity of cartooned unexpanded plastic.Sprinkler pipes with outside diameter less than 60 mm or the barriers with similar size do not have obvious effect on the performance of K202 upright ESFR sprinkler.
What problem does this paper attempt to address?