Approach to Simulation Model of Ferroresonance

LEI Juan,GUO Jie,GAO Yuan,YU Fang
DOI: https://doi.org/10.3969/j.issn.1003-8337.2007.04.009
2007-01-01
Abstract:In order to calculate the ferroresonance overvoltage in neutral ungrounded distribution system which is resulted from the saturation of the electromagnetic voltage transformer(PT),it is necessary to establish the exact equivalent model of the PT.It shows the excitation curve of a 10 kV PT through the test date of the no-load by the no-load test on the PT.Simulation is done on two different PT models,one model which doesn't consider the effect of hysteresis and the other one simulates the effect.Through analyzing of the error of calculation results of simulation,the conclusion is that hysteresis loss have an distinct damping effect on each phase overvoltage of PT when high and fundamental frequency resonance appear in system,when high frequency resonance appears,through using the model considering hysteresis,the maximal overvoltage of each phase reduces about by 41%,31% and 42% respectively as compared with ignoring hysteresis,when fundamental frequency resonance appears,voltage of the lower voltage phase reduces about 27%.When fractional frequency resonance appears in system,hysteresis have an little effect.It is obvious that the calculation result which uses the model considering hysteresis to simulate is more accuracy.