Modeling Method of High-frequency Equivalent Circuit of Current Transformer for Overvoltage Detection
LIU Bowen,ZOU Guoping,WEI Xingchang,YANG Zhi,ZHENG Yiming
DOI: https://doi.org/10.13296/j.1001-1609.hva.2023.03.021
2023-01-01
Abstract:The insulation performance of equipment in the power system is very important,and overvoltage is one of the main threats that cause insulation damage of the equipment. The use of current transformers can effectively monitor the overvoltage in the power system. In this paper,a kind of high-frequency equivalent circuit modeling method of current transformers for overvoltage sensors based on last-screen current detection is proposed to solve the problem that low-frequency current modeling methods has no way to accurately simulate the intermediate and high-frequency(MHz)components of overvoltage. The method can,on the premise not changing the primary wiring mode of power equipment,achieve accurate modeling of various overvoltage sensors including power frequency overvoltage,operating overvoltage and lightning overvoltage. Firstly,the electromagnetic resonance characteristics of the current transformer at high frequency are analyzed and,on this basis,the RLC high-frequency equivalent circuit containing multiple resonance frequencies is set up. Then,through simulation examples and experimental tests,the accuracy of the proposed model is verified. The proposed equivalent circuit can be used to calculate the magnitude of the overvoltage according to the last screen current of the current transformer,thus effectively assessing the insulation risk and assuring safe operation of the power grid.