Performance Measurement of VAV Air System with Different Control Methods

LIU Jian,CHENG Shi-bai,CHEN You-ming,Cary H.K.Chan,Jean Qin,ZHOU Qiang
DOI: https://doi.org/10.3969/j.issn.1005-0329.2013.04.016
2013-01-01
Abstract:The control method of variable air volume(VAV) system in an office building in Hong Kong was transformed.Two typical days in the winter and summer were selected,respectively.The performance of the duct static pressure reset control supply air temperature reset control and constant duct static pressure control constant air temperature control method was tested in an existing office building in Hong Kong.The operations of the system with two control methods are compared.Coefficient of transformation is introduced to evaluate the energy saving effect.ADPI is adopted to evaluate the indoor thermal comfort.Results show that the indoor thermal comfort is improved apparently when the duct static pressure reset control is adopted.Duct static pressure reset control supply air temperature reset control at part load energy saving effect is more obvious.