Climate Compensation and Indoor Temperature Optimal Measuring Point Energy Saving Control in VAV Air-Conditioning System

Xiuying Yan,Cong Liu,Meili Li,Ating Hou,Kaixing Fan,Qinglong Meng
DOI: https://doi.org/10.3390/en12224398
IF: 3.2
2019-11-19
Energies
Abstract:Temperature measuring point is the key to room environment control. Temperature measuring points and climate changes are directly related to the room control effect. It is of great theoretical and practical significance to study the temperature measuring points and control strategy based on climate compensation. In this study, first, the climate compensation concept in a heating system was introduced into a variable air volume (VAV) air-conditioning system. The heating load was modeled as a function of supply air temperature by analyzing the heat exchange. Based on each control link of subsystems, a climate compensation scheme is proposed to determine the optimal set-point of the supply air temperature. At the same time, a layout of multiple temperature measuring points of an air-conditioned room was studied. Furthermore, the optimal indoor temperature measuring point was determined using an adaptive weighted fusion method. Finally, simulation results show that the proposed method has better control effects on indoor temperature adjustment compared with the traditional method. The optimal supply air temperature in summer and winter was determined according to the proposed climate compensation scheme, and the supply air temperature was controlled using an improved single-neuron adaptive control strategy. Experimental results show that the maximum energy saving can reach up to 35.5% in winter and 6.1% in summer.
energy & fuels
What problem does this paper attempt to address?