Performance comparison between temperature and humidity independent control and conventional air conditioning systems

Zhang Haiqiang,Liu Xiaohua,Jiang Yi
DOI: https://doi.org/10.3969/j.issn.1002-8501.2011.01.010
2011-01-01
Abstract:Selects a typical office building located in Beijing and Guangzhou respectively as the comparison object.Conventional air conditioning system(CAS) adopts typical system of fan coil units plus dedicated outdoor air.Calculates the annual hourly cool load by DeST software,and calculates the EERs and energy consumption of the two systems.As a result,when the office building is located in Beijing,the annual energy consumption is 14.75 kWh per square metre,and the EER is 4.5 for temperature and humidity independent control air conditioning system(THICS),while the annual energy consumption is 18.63 kWh per square metre and the EER is 3.6 for CAS.For that office building in Guangzhou,the corresponding value is 32.66 kWh per square metre and 4.5 for THICS,while 43.39 kWh per square metre and 3.4 for CAS.Comparing with CAS,the THICS can reduce energy consumption by 20% to 30%.