Comparison of EERt between different terminal devices of air systems

Han Zheng,Zhu Yingxin
DOI: https://doi.org/10.3969/j.issn.1002-8501.2009.02.015
2009-01-01
Abstract:Compares the rated, designed and practical EERt(energy efficiency ratio of terminal system) of different terminal devices between three typical air systems—fan coil unit plus outdoor air handle unit system (FCU+OA), constant air volume system (CAV), variable air volume system (VAV). Calculates the EERt with and without consideration of outdoor air handle unit system of each air system. Compares the designed and practical EERt among several large public buildings. Compared with rated parameters, designed EERts decrease about 50% in actual design projects. The energy consumption of FCU+OA system is about 50% of that of all-air system for the same cooling supply in design. Practical EERts are usually less than design parameters except in well designed VAV system. As a result of cases study, the practical EERt of FCU+OA system is around 13, that of VAV system is 6 and that of CAV system is 4.