Performance test and analyses of temperature and humidity independent control air conditioning system in an office building in Shenzhen
Liu Shuanqiang,Liu Xiaohua,Jiang Yi,Liu Xin,Li Haixiang,Chen Xiaoyang,Qiang Bin,Yang Haibo
DOI: https://doi.org/10.3969/j.issn.1002-8501.2011.01.012
2011-01-01
Abstract:Presents the performance test of the main equipment of this temperature and humidity independent control air conditioning system(THICS).The test results show that the average COP of the liquid desiccant fresh air unit is about 5.4,and that of the high temperature chiller is about 8.9,while the EER of the water system is 5.1,the indoor air parameters of the typical room fit the design value very well,and the dew-point temperature of the indoor air is lower than the water supply temperature,the dry coil resulting no condensation.The annual average power consumption of the THICS is 34.3 kWh per square metre,about 69.3% of that of A-grade office building in Shenzhen.