Experimental Investigation on Energy and Materials Savings of Intermediate Cooler Used in the Compressor Cold System

Sun He,Tan Xianghui,Zeng Liding,Zhu Dongsheng
DOI: https://doi.org/10.3969/j.issn.1671-6612.2012.03.004
2012-01-01
Abstract:Intermediate cooler's primary function is to rule out the gas heat generated by the compression process.It is important to improve the efficiency of the compressor equipment.Form the point of the view on the heat transfer resistance,the air resistance is more than 80% in the shell and the pressure drop is high,so the consumption of the fan or compressor is large.To increase the heat transfer performance on the intermediate cooler,the key is to strengthen the air convection of the shell and reduce the pressure drop.This article is focuses on the air-side heat transfer technologies used to produce energy efficiency and material savings,create the test plate form for the two intermediate coolers,by changing the mass flow of the air in the shell,circulating water temperature and flow rate in the pipe and other parameters to test the thermal performance and pressure drop.The experimental results show that the twisted tube intermediate cooler on the heat transfer performance is better than the conventional smooth tube segmental baffles intermediate cooler about 35%-87%,the low number is particularly significant.It will be a guide of the optimization design of the compressor cooling system.