Study on Performance Matching and Zeotropic Characteristics of Non-ozone Depleting Refrigerant Mixture for Heat Pump

Zan Cheng,Shi Lin
DOI: https://doi.org/10.3969/j.issn.0253-4339.2008.04.002
2008-01-01
Abstract:A refrigerant mixture with 0 ODP for moderately high temperature heat pumps, named HTR04 (High Temperature Refrigerant 04), has been developed. Three key problems for the application of HTR04 were investigated, i.e., its direct replacement use in a R134a compressor, its composition shift and temperature glide. The results indicate that the heat pump with an original compressor could provide hot water with about 80oC by filling HTR04 to replace R134a. The changes of the system performance caused by HTR04 composition shift could be accepted in use. The coefficient of performance could be improved through optimal matching of the glide temperature and the temperature difference of water in the condenser.
What problem does this paper attempt to address?