Abstract:HFO-1336mzz(Z)is considered as a promising substitution for its excellent environmental performance (ODP=0,GWP=2).The cycle performance of HFO-1336mzz(Z) and HCFC-123 under different heat pump conditions is investigated from theory and ex-periment.The results show that the calculated results has a good agreement with the ex-perimental results.Under various evaporating temperatures,for HFO-1336mzz(Z)and HCFC-123,the pressure ratio,power consumption,heating capacity and discharging tem-perature of heat pump cycle increase with the rising of the condensing temperature.Al-though the pressure ratio of HFO-1336mzz(Z)heat pump cycle is greater than that of HCFC-123 heat pump cycle,it has a lower power consumption and a smaller heating ca-pacity.In the theoretical analysis,their COP of heat pump are close,while the COP of HFO-1336mzz (Z)heat pump is lower than that of HCFC-123 heat pump by 3.9%-8.9%in the test.HFO-1336mzz (Z)has better comprehensive performance applied to the heat pump system than HCFC-123.