Identification Method for Excitation Inductances of Three-phase Three-limb Transformer Based on Characteristics of Magnetic Circuit

XU Liqiang,JIAO Zaibin,DU Bin
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2011.19.014
2011-01-01
Abstract:For the application of excitation parameters in transformer protection,the inductance identification method of three-phase three-limb transformer was proposed.Based on the characteristic of magnetic circuit,a mathematic model which links the voltages induced by the main fluxes and the currents of the windings was established.For transformers with Y/Y connection,using main flux induced voltage,the excitation inductances can be calculated accurately and steadily under conditions of normal operation,inrush current and external faults,and the characteristics are distinct from internal faults.The delta side circulating current is no part of excitation currents of three-phase three-limb transformers,so with main flux induced voltage replaced with winding voltage,the proposed method can be applied to transformers with Y/? connection directly.In this case,the excitation inductances can be calculated under inrush condition,and can be taken as identification criterion for inrush current in differential protection of the transformer.The proposed method is validated by unified magnetic equivalent circuit(UMEC) transformer model.
What problem does this paper attempt to address?