The Bottom Ash and Air Supply System of a Circulating Fluidized Bed Boiler

Jin-wei WANG,Jun-fu LU,Bao-zhong ZHANG,Guang-xi YUE
DOI: https://doi.org/10.3969/j.issn.1672-4763.2006.01.006
2006-01-01
Abstract:Based on the Circulating Fluidized Bed Boiler principle,combining the operating practices of more than 100 CFB Boiler,the bottom ash drain,air supply,and fuel and limestone characteristics are conducted in this paper.The concept of effective bed inventory,the principle of bed inventory control and the selection theory of primary fan pressure are suggested.The authors believe that the pressure drop of the primary nozzle is the key to prevent bottom ash fall down.The continuous bottom ash drain under air distributor with fluidized bed ash cooler is necessary for some case to maintain the mass balance with selective ash.Considered the fuel and operation flexibility,the flow rate margin should be 25 % for both the forced fan induced fan,while the pressure margin 1.3 and 1.2 for the forced fan induced fan,respectively.If the boiler fuel is biomass,the margin should be more.
What problem does this paper attempt to address?