Commercial and Experimental Study of a Rotor-assembly Type Intensified Heat-transfer Device at the Tube Side

杨卫民,李锋祥,陈胜利,阎华
2008-01-01
Abstract:Current urgent demands for energy-saving and consumption reduction were described along with the technical theory of a rotor-assembly type intensified heat-transfer device—Clean-energy Core. The above device has been installed on the 2# turbo-generator unit of Datang Jiamusze No.2 Power Plant. The condenser at one side of the turbo-generator unit was provided with the device in question while the condenser at another side of the unit was not. The performance test content,testing method and the calculation results of the two condensers of the No.2 power plant were discussed. The performance of the two condensers and the cost-effectiveness of the No.2 unit after installation of the device on one condenser were calculated and analyzed. After the installation of the above-cited device,the terminal temperature difference of the relevant condenser drops by 2.79 ℃,its vacuum increases by 2.97 kPa and its cooling water flow rate decreases by 9.8%. Under the condition of the condensers having the same inlet water temperature and vacuum,the load bearing capacity of the turbo-generator unit will increase by 19.7%,and the water resistance of the condensers increase by 19.52 kPa. The results of the industrial experiments and analytic calculation show that the rotor-assembly type intensified heat-transfer device can be used for condensers in power plants to improve their performance.